Product categories
Our products
MPC type marine assembled air conditioner
Marine assembled air-conditioning unit is the core equipment of the ship's air-conditioning system.
Marine assembled air-conditioning unit is the core equipment of the ship's air-conditioning system. It can be used to adjust the temperature and humidity of the air and provide people with a comfortable working and living environment. It is widely used in various types of passenger ships, cargo ships, ships and marine The oil platform has the characteristics of novel design, convenient operation, stable operation, safety and reliability. The device has undergone pressure test, vacuum test and operation test before leaving the factory. When installing in the shipyard, it is only necessary to connect the power supply and connect the necessary related pipelines to debug and put into operation.
*The cooling capacity is the cooling capacity under the condition that the air temperature outside the cabin is 35°C, the relative humidity is 70%, and the fresh air ratio is 40%; the air temperature inside the cabin is 27°C, and the relative humidity is 50%.
*The heating capacity of the steam heater is the heating capacity under the condition that the air temperature outside the cabin is -20°C, the relative humidity is 50%, and the fresh air ratio is 40%; the air temperature inside the cabin is 20°C, and the relative humidity is 50%.
*The static pressure outside the machine is the static pressure inside the air outlet.
*Specific size and requirements can be customized according to the user's situation, in order to meet the needs of different users to the greatest extent.
● 50mm thick box has higher structural strength
● Carrier, Bock, Biter piston, screw compressors are optional
● Through the communication signal line, collect the temperature and humidity signals from the return air of the air-conditioning unit to achieve independent adjustment
● High-efficiency heat exchangers
● Full security features
● The air volume range reaches 2000~24000m3/h
Model/Item
|
MPC-2
|
MPC-2.6
|
MPC-3
|
MPC-3.3
|
MPC-4
|
MPC-5
|
MPC-6
|
MPC-7
|
MPC-8
|
MPC-10
|
MPC-13
|
MPC-16
|
MPC-20
|
MPR-24
|
|
Cooling energy KW
|
23.2
|
30.2
|
35
|
38.4
|
46.4
|
58
|
70
|
81.4
|
93
|
116
|
151
|
186
|
240
|
280
|
|
Heating KW
|
26.7
|
35
|
39.5
|
44.2
|
53.5
|
67.44
|
81.4
|
93
|
107
|
134
|
167
|
215
|
265
|
300
|
|
Nominal air volume m3/h
|
2180
|
3710
|
3710
|
3710
|
4240
|
5010
|
6310
|
7160
|
8200
|
10500
|
12350
|
16100
|
18000
|
24000
|
|
External static pressure Pa
|
440
|
540
|
540
|
540
|
700
|
1030
|
1180
|
1470
|
1570
|
1700
|
1800
|
1760
|
1800
|
2000
|
|
Refrigeration medium
|
R404A, R134a, R407C, R22
|
||||||||||||||
Heating medium
|
0.3~0.4Mpa saturated steam
|
||||||||||||||
Power
|
Main circuit AC380V 3Ф 50Hz Control circuit, AC220V 1Ф 50 Hz
|
||||||||||||||
Compressor
|
type type
|
Totally Hermetic Compressor
|
Semi-closed piston or screw type
|
||||||||||||
Energy adjustment (%)
|
0, 50, 100 (or 0, 66, 100)
|
||||||||||||||
Motor power (KW)
|
6.5
|
3.82╳2
|
10
|
4.99╳2
|
11
|
15
|
19
|
22
|
26
|
30
|
37
|
45
|
70
|
75
|
|
fan
|
Style
|
Marine centrifugal fan
|
|||||||||||||
Motor power KW
|
2.2
|
2.2
|
3
|
2.2
|
3
|
5.5
|
5.5
|
7.5
|
11
|
11
|
15
|
15
|
22
|
37
|
|
Condenser
|
Style
|
||||||||||||||
Inlet water temperature (℃)
|
≤32
|
||||||||||||||
Cooling water flow (m3/h)
|
6
|
7
|
10
|
10.5
|
12
|
15
|
18
|
21
|
24
|
30
|
40
|
50
|
70
|
80
|
|
Water pressure loss KPa
|
30
|
35
|
40
|
45
|
45
|
50
|
60
|
65
|
70
|
75
|
80
|
90
|
100
|
105
|
|
Evaporator type
|
Copper tube copper sleeve
|
||||||||||||||
Heater
|
Style
|
Copper tube copper sleeve
|
|||||||||||||
Steam consumption kg/h
|
46
|
60
|
68
|
76
|
92
|
115
|
138
|
160
|
184
|
230
|
290
|
368
|
454
|
517
|
|
Humidifier
|
Style
|
Steam spray
|
|||||||||||||
Steam consumption kg/h
|
8
|
10
|
12
|
12
|
16
|
20
|
24
|
28
|
32
|
40
|
52
|
64
|
76
|
88
|
|
Air filter
|
Concave-convex nylon mesh or aluminum alloy, removable and washable
|
||||||||||||||
Safety device
|
High pressure, low pressure, oil pressure, water pressure, overload protection, safety valve (MPC-2, 2.6, 3.3 without oil pressure protection, fusible plug instead of safety valve)
|
||||||||||||||
Dimensions
|
Lmm long
|
2000
|
1800
|
2100
|
2100
|
2100
|
2330
|
2600
|
2800
|
2800
|
2900
|
3500
|
3800
|
4300
|
4000
|
Width Bmm
|
1050
|
960
|
1050
|
1200
|
1050
|
1850
|
1850
|
1950
|
2050
|
2150
|
2350
|
2600
|
2000
|
2000
|
|
Height Hmm
|
1900
|
1750
|
1900
|
1750
|
1810
|
1750
|
1600
|
1750
|
1750
|
1750
|
1800
|
1900
|
2300
|
2100
|
|
Weight kg
|
~1200
|
~1400
|
~1400
|
~1400
|
~1500
|
~1700
|
~1900
|
~2150
|
~2300
|
~2800
|
~3200
|
~4100
|
~4500
|
~4600
|
Messages
Related products
MCU type marine compressor condensing unit
CSIC TianHe Marine Equipment Jiangsu Co.,Ltd.
Service Hotline:
Fax:
0523-87735588
Contact Address:
16-18 Tianhe Road, Industrial Park, Cheng District, Taixing City, Jiangsu Province
2022 CSIC TianHe Marine Equipment Jiangsu Co.,Ltd. www.300.cn 苏ICP备13015743号-1 苏公网安备 32128302000375号 SEO Business license